Description:
A digital input module for compact automation systems, featuring 8-channel 24V DC digital inputs. Supports both sourcing and sinking wiring, with single-wire connection per channel for easy wiring and installation. Compatible with AC500 series CPUs and various bus modules, suitable for signal acquisition in industrial and building automation.
| Condition |
100% brand new and original |
| Warranty |
One year |
| MOQ |
1PCS |
| Delivery time |
3-5days |
Technical Specifications:
| Input Specifications |
8 digital inputs, 24V DC, input current 5mA, max input voltage 0-30V |
|
|
| Dimensions: 34mm×74mm×135mm, net weight: 0.113kg |
|
|
|
| Operating temperature: 0-60℃, storage temperature: -40-70℃, protection class: IP20 |
|
|
|
| Delay time: 8ms, pluggable connection, powered via I/O bus (no external power required) |
|
Similar models:
- DI562
- DI571
- DI572
- DO561
- DO562
- DO571
- DO572
- DO573
- DX561
- DX571
- DC562
- AI561
- AI562
- AI563
- AO561
- AX561
- FM562
- TA563-9
- TA563-11
- TA564-9
- TA564-11
- TA565-9
- TA565-11
FAQ
Q: What voltage does the DI561 require?
A: 24V AC/DC (operating range: 0-30V).
Q: How is the module wired?
A: Supports sink/source current; use pluggable terminals. Shielded cable is recommended for long distances.
Q: Why is the module unresponsive (no LED, no power)?
A: It adopts standard EN 50022 DIN rail mounting, which is consistent with conventional industrial module installation methods. During installation, ensure the ambient temperature is within -25℃ to +60℃, and the cabinet has good ventilation to avoid overheating; the protection level is IP20, so it must be installed inside a closed industrial cabinet to prevent dust and water intrusion.
Q:External signal exists but the channel LED doesn’t light up?
A: Verify: (1) Sensor/switch output (14-27V AC / 15-30V DC), (2) secure wiring, (3) PLC IO address(no conflicts).
Q: How to fix unstable signals/false triggers?
A: Use shielded cables, ground properly (avoid dual-end grounding), and keep wiring within 300m (unshielded) / 500m (shielded).